Wave Examples
Below are a few wave examples of power quality issues that we have captured in a few of our Power Quality sessions. Today’s electronics are more susceptible to damage resulting in a shortened life span as well as misoperation of equipment. Depending on your equipment’s needs and your electrical environment we can advise on mitigation applications to keep your system running smooth.
Images for reference only – click to enlarge image
Example A: Single Phase
This wave example shows a good clean voltage and current (sinusoidal) waveform on 1 phase of the electrical environment.
Example B: 3 Phase
For comparison, this is the same reading as example A only we have expanded to all phases of the typical 3 phase environment. Having a balanced load over all 3 phases in your system is desirable. In the bottom graph (amps) you will note that all phases are within 10% of each other which is optimum.
Example C: Electronic Load Differences.
With today’s electronics influences, current draws are no longer sinusoidal as shown in the lower graph section. This leads to harmonics in your system. You can also see the punch down effect this has on the voltage waveforms as noted in the upper graph section.
Example E: Short Duration Phase Drop Out – Beginning
This wave example shows the start of a 2 second utility interruption. These interruptions will affect systems differently.
Example F: Short Duration Phase Drop Out – End
This examples continues to follow the sinewaves of example E, as the utility interruption corrects and stabilizes about 2 seconds later. Damages typically occur during the end of these interruptions, as shown in the lower amps graph taking a hard hit (current surge) to the system.
Example G: Worn Out Contactor.
In review of the readings we collected here we could see that when a piece of equipment was starting it was affecting the voltages of all 3 phases. A worn out contactor was needed to be replaced.